STT750 Smart Temperature Transmitter

STT750 Temperature Transmitters are suitable for a wide range of control and safety applications, the transmitters provide users with the benefits of the SmartLine platform, including modularity, easier maintenance and lower total cost of ownership

Well-suited for industrial process control where precision and stability are needed. Good choice for safety instrumented systems given its SIL 2/3 compliance. Useful in environments with electrical noise, thanks to galvanic isolation. Because of it’s modular design, it’s cost-effective in maintenance-heavy setups (easy to swap modules). High isolation voltage (e.g., 2000 VDC between input, output, and ground) for noise protection. Polarity-insensitive 2-wire loop allows flexibility in wiring

Accuracy & Stability

Digital accuracy up to ± 0.14 °C for RTD inputs.

Long-term stability: ± 0.01% of upper range limit (URL) per year, for up to 10 years.

Response / Update Time

~125 ms update time for single‐input models.

~250 ms for dual-input variants.

Universal Input

Supports a wide variety of sensors: RTD, thermocouple, mV, and resistance (ohm).

Some models support dual-sensor input (for redundancy, averaging, or differential measurement).

Reliable Measurement

Built-in galvanic isolation to reduce noise.

Dual-compartment housing separates electronics/display from wiring.

Sensor break detection to detect open/failed sensor.

Comprehensive on-board diagnostics to monitor health of transmitter and sensor.

Safety / Functional Compliance

Compliant with SIL 2 / SIL 3 for safety instrumented systems.

Supports NAMUR 89 wire break detection.

Communication / Output

4–20 mA analog output.

HART 7 communication for digital configuration / monitoring.

Display / Configuration

Modular alphanumeric LCD display (optional, field replaceable).

Display can be rotated (0°, 90°, 180°, 270°) for optimal viewing.

Supports up to 8 configurable display screens on basic LCD.

Integral three-button configuration (zero, span, setup) + optional external buttons.

Support for entering Callendar–Van Dusen coefficients (R0, α, β, δ) for calibrated RTDs.

Design & Maintenance

Modular design: electronics, temperature board, display, and communication modules can be swapped without losing calibration or performance.

Polarity-insensitive loop wiring (works even if wiring is reversed).

Certifications / Approvals

Hazardous-area approvals: FM, CSA, ATEX, IECEx.

EMI / EMC: complies with relevant standards per model.

Warranty: up to 3 years

Features

  • Single universal input
  • Digital accuracy up to 0.14°C for RTD
  • Easy-to-use-and-read basic display
  • Transmitter and sensor diagnostics
  • HART7 communications
  • Full compliance with SIL 2/3 requirements
  • Up to a 3-year warranty
  • FM/CSA/ATEX/IECEx approvals.