OPTITEMP TT 51 R

Rail-mounted temperature transmitter with universal dual input, galvanic isolation, HART® and SIL

  • Input: RTD, TC, mV, Ω
  • Output: 2-wire, 4…20 mA/HART®
  • Programmable via PC or HART® handheld communicator
  • Accuracy: ±0.05%

The OPTITEMP TT 51 R is a universal, programmable high-performance 2-wire rail-mounted temperature transmitter with HART® communication. The galvanically isolated dual input device works with RTD elements, thermocouple (TC) elements or other inputs (mV and Ω). The device is available in 2-, 3- or 4-wire circuit. It also features the option of a 4-wire circuit for two Pt100 inputs. The transmitter stands for proven stability, reliability as well as high accuracy and boasts a minimum measuring error of ±0.05% of span in 5 years. The transmitter offers extended diagnostic information (e.g. open or short circuit monitoring etc.). Its unique “SmartSense” function allows insulation resistance monitoring to prevent measuring errors.

Product positioning

With universal dual input, galvanic isolation, HART® and SIL

Product variants Standard

OPTITEMP TT 51 R

EX: OPTITEMP TT 51 R Ex

Transmitter programmable

Yes

Ambient temperature

-20…70°C/-4…158°F

Transmitter input

Potentiometer (Ω), Resistance (RTD), Thermocouple (TC), Voltage (mV)

Galvanic isolation Yes

Galvanic isolation (VAC) 1500 VAC

Galvanic isolation (VAC) 1500 VAC

Power supply (VDC)

10…36 VDC

10…30 VDC (Ex)

RTD input Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, Cu10

Potentiometer input (Ω) 100…4000 Ω

Voltage input (mV) -10…+1000 mV

RTD input / wiring 2-wire, 3-wire, 4-wire

TC Input B, C, D, E, J, K, N, R, S, T

Configuration method

HART handheld, PC/ConSoft software

Transmitter mounting

Rail-mounted

Diagnostic functions

Isolation monitoring (SmartSense), Sensor backup function, Sensor break detection, Sensor drift detection, Sensor error correction, Sensor short circuit detection, Signal filtering function

Approvals/Standards

Certificates/Approvals Ex ATEX, IECEx

Certificates/Approvals Safety SIL 2

NAMUR compliance NE 107, NE 21, NE 43, NE 53, NE 89

Communication

Analogue outputs 4…20 mA

Digital outputs HART®

Features & Options

Product features and options depend on device configuration: Contact us to make sure that your preferred functionality can be combined in one device.

  • Highly precise, completely universal digital device, with dual sensor input
  • Configuration, installation and maintenance via software ConSoft, HART® protocol or EDD
  • Optional redundant 4-wire circuit for 2 x Pt100
  • Best in class for long-term stability: ±0.05% of span in 5 years
  • Fast response time, high speed update (300 ms)
  • High reliability due to 50-point linearisation, sensor drift detection and sensor backup
  • Sensor break monitoring, failure detection and error correction
  • Isolation resistance monitoring (SmartSense): fail-safe up to 95% relative air humidity
  • Rugged design: vibration-resistant up to 10 g
  • Galvanic isolation: 1500 VAC
  • Conforms to NAMUR in accordance with NE 43, NE 53, NE 89, NE 107
  • Conforms to EMC in accordance with EN 61326 and NE 21
  • SIL2 certified
  • Can be configured via ConSoft while staying connected with a sensor installed in hazardous areas
  • Designed for installation on a rail (in accordance with DIN EN 60715)
  • Available as intrinsically safe: ATEX, IECEx (zone 0, 1, 2)Optional rail mounting kit for installation on a DIN rail (in accordance with DIN EN 60715)