Promag H is the preferred sensor for hygienic applications with highest requirements in the food and beverage and life sciences industries. With its compact transmitter Promag H 300 offers a high flexibility in terms of operation and system integration: access from one side, remote display and improved connectivity options. Heartbeat Technology enables compliance and process safety at all times. The bidirectional measuring principle is virtually independent of pressure, density, temperature and viscosity. Dedicated to demanding applications in the food and beverage as well as in life sciences industries.
Specialist for hygienic applications with a compact, easily accessible transmitter. Dedicated to demanding applications in the food and beverage as well as in life sciences industries.
DN 2 to 150 (¹⁄₁₂ to 6″)
Liner: PFA
Electrodes: 1.4435 (316L); Alloy C22, 2.4602 (UNS N06022); Tantalum; Platinum
Process Connections: stainless steel, 1.4404 (F316L); PVDF; PVC adhesive sleeve
Seals: O-ring seal (EPDM, FKM, Kalrez), aseptic molded seal (EPDM, FKM, silicone)
Grounding Rings: stainless steel, 1.4435 (316L); Alloy C22, 2.4602 (UNS N06022); tantalum
Volume flow, temperature, conductivity, mass flow, corrected volume flow, corrected conductivity
Volume flow (standard): ±0.5 % o.r.± 1 mm/s (0.04 in/s)
Volume flow (option) ±0.2 % o.r. ± 2 mm/s (0.08 in/s)
0.06 dm³/min to 600 m³/h (0.015 gal/min to 2 650 gal/min)
PN 40, Class 150, 20K
–20 to +150 °C (–4 to +302 °F)
–40 to +60 °C (–40 to +140 °F)
1.4301 (304), corrosion resistant
AlSi10Mg, coated; 1.4409 (CF3M) similar to 316L; stainless steel for hygenic transmitter design
IP66/67, type 4X enclosure
IP69
4-line backlit display with touch control (operation from outside)
Configuration via local display and operating tools possible
Remote display available
Status input
4-20 mA input
HART, PROFIBUS DP, PROFIBUS PA, FOUNDATION Fieldbus, Modbus RS485, PROFINET, PROFINET over Ethernet-APL, Ethernet/IP, OPC-UA
DC 24 V
AC 100 to 230 V
AC 100 to 230 V / DC 24 V (non-hazardous area)
ATEX, IECEx, cCSAus, INMETRO, NEPSI, EAC; JPN, UK Ex, KC
CE, C-tick, EAC marking
Functional safety according to IEC 61508, applicable in safety-relevant applications in accordance with IEC 61511
Calibration performed on accredited calibration facilities (acc. to ISO/IEC 17025)
Heartbeat Technology complies with the requirements for measurement traceability according to ISO 9001:2015 – Section 7.1.5.2 a (TÜV SÜD attestation)
LR approval, DNV approval, ABS approval, BV approval
PED, CRN
3.1 material
Sanitary approval: EHEDG, 3-A, liner and seals acc. to FDA, cGMP
Flexible installation concept – numerous hygienic process connections. Energy‐saving flow measurement – no pressure loss due to cross section constriction. Maintenance‐free – no moving parts. Liner made of PFA. Sensor housing made of stainless steel (3-A, EHEDG).
Full access to process and diagnostic information – numerous, freely combinable I/Os and fieldbuses. Reduced complexity and variety – freely configurable I/O functionality. Integrated verification – Heartbeat Technology. Wetted materials CIP, SIP cleanable. Compact hygienic dual-compartment housing with IP69 and up to 3 I/Os. Backlit display with touch control and WLAN access.